Ultron (> 10kVA)
 

NT Series 20-500 kVA

     
 
Ultron (> 10kVA) - NT Series 20-500 kVA

Enterprise power customized for greatest reliability

Designed for operations in the harshest of environmental conditions, the Ultron NT Series UPS is an industrial UPS system offering proven reliability and flexibility to secure electrical power supplies in critical applications.

The three phase UPS featuring customized I/P-O/P ratings brings best-in-class technology, a long product lifetime (minimal servicing), N+X parallel operations for increased redundancy deployment, and a broad range of available power ratings.

The Ultron NT Series UPS lets you effectively respond to increasing demands placed on infrastructure in commercial and industrial facilities by offering N+1 functionality. Efficiency is a key feature with 93% system efficiency at full load and continuing to 25% load.

In an era where big data is dominant, increased power protection requires a solution with unmatched power performance. The Ultron NT Series UPS system fulfills your uninterruptible power requirements.
 
     
 
 
 
Available from 20 to 4,000 kVA (8 x 500 kVA in parallel).
Parallel redundancy without requiring extra hardware to increase reliability.
Optional harmonic filter and 12-pulse rectifier.
Redundant auxiliary power and control circuit ensures higher reliability.
Inbuilt maintenance and static bypass switch.
Multi-language LCD display and LED status indicators.
RS232, RS485 and six programmable dry contact outputs.
Compatible with generator installation and unbalanced loads.
Optional external battery cabinet for longer backup time.
Parallel expansion as your business grows and consequently saves initial investment.
Wide input voltage range extends battery lifetime.
Economy mode saves energy and operating cost.
Common battery installation saves initial investment.
 
 
 
 
 
     
 
Specifications
 
 
 
 
Model
NT-20K / NT-30K / NT-40K / NT-50K
NT-60K / NT-80K / NT-100K / NT-120K
NT-160K / NT-200K / NT-260K
NT-320K / NT-400K / NT-500K
Power Rating
NT-20K : 20kVA / 16kW
NT-30K : 30kVA / 24kW
NT-40K : 40kVA / 32kW
NT-50K : 50kVA / 40kW
NT-60K : 60kVA / 48kW
NT-80K : 80kVA / 64kW
NT-100K : 100kVA / 80kW
NT-120K : 120kVA / 96kW
NT-160K : 160kVA / 128kW
NT-200K : 200kVA / 160kW
NT-260K : 260kVA / 208kW
NT-320K : 320kVA / 256kW
NT-400K : 400kVA / 320kW
NT-500K : 500kVA / 400kW
Input
Nominal Voltage : 208/120; 380/220; 400/230; 415/240; 480/277 Vac (3 phase, 4-wire + G)
Voltage Range : 305~499 Vac
Current Harmonic Distortion : < 3% (with optional power filter, full load)
Frequency : 45~65Hz
Output
Voltage
208/120, 380/220, 400/230, 415/240, 480/277 Vac (3 phase, 4-wire + G)
220, 230, 240 Vac (1 phase, 2-wire + G)*
Output Power Factor : 0.8
Voltage Harmonic Distortion : ≤ 3% (linear load)
Voltage Regulation : ± 1% (static)
Frequency
50/60 Hz ± 0.01% (internal oscillator)
50/60 Hz ± 1% (synchronized)
Overload Capability
≤ 110%: 60 minutes
110 ~ 125%: 10 minutes
126 ~ 150%: 1 minute
Interface
Standard : RS232 x 1, RS485 x 2, SMART slot x 1, Output dry contact x 6
Other Features
Parallel Redundancy : Up to 8 units
Emergency Power Off : Local and remote
SRAM Event Log : 500 records
Input Harmonic Improvement : Optional harmonic filter and 12-pulse rectifier
Efficiency
AC-AC
NT-20K : 90%
NT-30K~40K : 91%
NT-50K~60K : 91.5%
NT-80K~100K : 92%
NT-120K~200K : 92.5%
NT-260K~500K : 93%
ECO Mode
NT-20K : > 97%
NT-30~500K : > 97.5%
Environment
Operating Temperature : 0 ~ 40ºC
Relative Humidity : 0 ~ 95% (non-condensing)
IP Protection : IP20
Audible Noise (at 1.5 meters)
NT-20K~40K : ≤ 60dB
NT-50K~120K : ≤ 65dB
NT-160K~200K : ≤ 68dB
NT-260K~400K : ≤ 72dB
NT-500K : ≤ 77dB
Physical-6pules
Dimensions(WxDxH) **
NT-20K~80K : 600 x 800 x 1400 mm
NT-100K~120K : 800 x 830 x 1700 mm
NT-160K~200K : 1200 x 830 x 1700 mm
NT-260K~400K : 1600 x 995 x 1950 mm
NT-500K : 1900* x 995 x 1950 mm
Weight
NT-20K : 365 kg
NT-30K : 365 kg
NT-40K : 425 kg
NT-50K : 460 kg
NT-60K : 506 kg
NT-80K : 525 kg
NT-100K : 700 kg
NT-120K : 745 kg
NT-160K : 1050 kg
NT-200K : 1085 kg
NT-260K : 1680 kg
NT-320K : 1720 kg
NT-400K : 1920 kg
NT-500K : 3110 kg*
* 500 kVA model is assembled into two cabinets: Inverter (width=1100 mm, 1760 kg) and Rectifier (width=800 mm, 1350 kg).

All specifications are subject to change without prior notice.
 
 
  Contact us
  Have a question or need any assistance that should be answered by a professional? Contact us, and let our staff help you.  
 
 
     
  Related Information
 
Success Stories
Awards and Recognition
 
 
 
 
RSS Feeds
Press Releases
 
Information
Privacy Policy Data Collection
Terms of use Contact us
 
Follow Us
© 2018 Delta Electronics, Inc. All Rights Reserved.